Fire Alarm Control Panel

YF-1 Fire Alarm Control Panel(5L~120L)

All interior components of the display module and base boards in the unit are approved by CE and CNS. All products have to pass strict inspection before delivery to ensure durability.
  • YF-1 Fire Alarm Control Panel(5L~120L)
  • YF-1 Fire Alarm Control Panel(5L~120L)
PRODUCT INFORMATION

Feature

  • Two-stage alarm delay function:
    At first stage, when the detector sends the signal for the first time, the control panel will automatically reset the signal and enter the second stage for standby after 8 seconds. At the second stage, if there is another signal sent by the detectors within 9-40 seconds, the control panel will triggerd the file alarm, else reset the alarm signal. This will prevent the control panel from sending false alarms.  

  • Standby battery protection: 
    During power-cut, when the standby battery is under DC 18V, it will automatically stop discharging to extend battery life.

  • Protection against lightning surge:
    Power supply module with protection against lightning surge to avoid device damage caused by high voltage or power surge. 

  • Quality control:
    All interior components of the display module and base boards in the unit are approved by CE and CNS. All products have to pass strict inspection before delivery to ensure durability.

  • Abnormal voltage inspection:
    With abnormal voltage display function, the system can indicate high and low voltage.

  • Modular design:
    The system has modular design with inputs/outputs independent terminal module. If there is a problem on site, users do not have to remove external wires and can easily replace defective boards improving the efficiency of maintenance and inspection.

  • Exterior design:
    Equipped with zone display panel board. The panel (made of flame retardant plastic) adopt a streamline design for clear indication of zone’s name, floor, building, properties, etc. 

  • Other Functions:
    Can be integrated with the TYY Voice Evacuation System and the Emergency Telephone System in one cabinet for more appealing look and less space consuming.


     

    Item Specification
    Model YF-1
    Cabinet Wall-mount
    Number of Loops 5L~120L
    Power Source 110V AC 50/60HZ or 220V AC 50/60HZ
    Standby Battery 24V DC
    Charging Voltage Below DC26V 450mA, trickle charging
    Circuit Voltage 24V DC operation voltage, under 10~11VDC  32mA
    Rated Impedance Under 50Ω, Ground Resistance above 2MΩ
     
    E.O.L Resistor 10KΩ
    No.of Indicators 1.2 times of the number of zone (LED indicating lamp)
    No. of Bells 1.2 times of the number of zone
    Cabinet Material Powder coating steel (optional Flame retardant ABS enclosure available up to 20L only).
    Main Alarm Audio Mono tone sounder (above 85dB for 1m distance)
    Alarm Relay Contact 2 sets of No-Voltage NO contact, capacity  AC  250V / 7A
    Dimensions(Steel)(mm) H 400 x W 300 x D 120